ELECTRICAL WIRING
10.3 ELECTRICAL WIRING BETWEEN INDOOR UNIT AND OUTDOOR UNIT
Connect the electrical wires between the indoor unit and the outdoor unit, as shown in next figure
Check to ensure that the terminal for power source wiring (terminals "L1" to "L1" and "N" to "N" of each terminal board) and
intermediate wiring (Operating Line: terminals "1" to "1" and "2" to "2" of each terminal board: DC5V) between the indoor unit and the
outdoor unit coincide correctly. If not, some component will be damaged.
1 Use shielded wires (≥0.75mm
size complied with local code.
2 Open a hole near the connection hole of power source wiring when the multiple outdoor units are connected from one power
source line.
3 The recommended breaker sizes are shown in the table of selecting the main switches.
4 In the case that a conduit tube for field-wiring is not used, fix rubber bushes with adhesive on the panel.
ELB
ELB
FUSE
Main switch
3N
400V 50Hz
1N
220-240V 50Hz
230V 50Hz
Operating line (shielded twist pair cable)
DC5V (Non-pole transmission H-LINK system)
Terminal Board
TB
Printed circuit board
PCB :
Field wiring
:
:
Field supplied
:
Optional accessory
10.4 WIRE SIZE AND MAIN BREAKER SWITCH

Electrical wiring connection. Field minimum wire sizes for power source
Model
Power Source
All indoor units
1~ 230V 50Hz
RPI-(8.0/10.0)FSN2E
RAS-8FSNM
RAS-10FSNM
3N~ 400V 50Hz
RAS-12FSNM
18
PMML0390B REV.0 - 11/2015 - P5416649
) for intermediate wiring to protect electrically noise obstacle at length of less than 1,000m and
2
Max 1 Outdoor Unit / Power Supply Line
The power source for outdoor units mus be made individually. If not, fire may occur in the worst case.
TB1
TB2
L1 L2 L3 N
1 2
L1 L2 L3 N
DC5V (Non-pole transmission H-LINK II system)
Distribution box or pull box
ELB
L1 L2 N
TB1
Nº 0 Indoor
TB2
1 2 A B
Maximum
Current
(A)
5.0
10.0
14.0
18.0
23.0
TB1
TB2
TB1
1 2
L1 L2 L3 N
Operating line (shielded twist pair cable)
Distribution box or pull box
L1 L2 N
TB1
Nº 1 Indoor
unit
Remote
TB2
control cable
1 2 A B
(Shielded
twist pair
cable)
Remote
control switch
(PC-ART)
Nº 0 System indoor units
Power Source
Transmitting
Cable Size
Cable Size
EN60 335-1 
EN60 335-1 
0.75 mm
2
0.75mm
1.5 mm
2
2.5 mm
2
4.0 mm
0.75mm
2
4.0 mm
2
TB2
1 2
unit
Remote
control cable
(Shielded
twist pair
cable)
Remote
control switch
(PC-ART)
Nº 1 System indoor units
CB(A)
6
2
16
20
30
2
30
ELB
Nº poles/A/mA
2/40/30
4/20/30