Mounting and installation instructions,
Connection of
The condenser is normally activated by a temperature controlled pool water pump,
water-cooled
which starts up automatically above a specified room temperature and pumps pool wa-
condenser
ter through the condenser.
The inflow is connected with the connector marked "IN" and the outflow with the con-
nector marked "OUT".
Connection of
Power is connected to the unit in accordance with the name plate. Please refer to the
power supply
wiring diagrams on page 121.
Important! All electrical connections must be made in accordance with local power sup-
ply company regulations!
Water quality
All electrical connections must be made in accordance with local power supply com-
pany regulations.
With addition of
The following guidance values are applicable to swimming pools with the addition of
chemicals
chemicals:
Free chlorine content
Combined chlorine content
pH
Total alkalinity
Calcium hardness
Total dissolved solids
Sulphates
Self-production of
The following guidance values are applicable to swimming pools with self-production of
chlorine
chlorine:
Salt (NaCl)
Total dissolved solids
pH
Total alkalinity
Calcium hardness
Sulphates
Langelier
It is advisable to use the Langelier Saturation index to ensure that the combination of
Saturation index
the different water parameters is acceptable.
Contact Dantherm Air Handling A/S if necessary.
Chemicals
Chemicals
continued
ppm
1,0-2,0
Max. 1/3 of free chlorine content
7,2-7,6
80-150
250-450
< 2000
< 360
ppm
2700-3400
< 5500
7,2-7,6
80-150
250-450
< 360
35