Herunterladen Inhalt Inhalt Diese Seite drucken

Wilo Para.../SC serie Einbau- Und Betriebsanleitung Seite 36

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Constant
speed (I, II, III)
H/m
III
II
I
External control
via iPWM signal
H/m
5 (95)%
% PWM 1 (% PWM 2)
15 (85)%
25 (75)%
35 (65)%
45 (55)%
55 (45)%
65 (35)%
75 (25)%
85 (15)%
n
¹/min
max
min
0 5
85 88
93
36
Recommended for systems with fixed system resistance
requiring a constant volume flow.
The pump runs in three prescribed fixed speed
stages (I, II, III).
NOTICE
Factory setting:
Constant speed, pump curve III
Q/m³/ h
The required setpoint/actual value comparison for con-
trol is performed by an external controller.
A PWM signal (pulse-width modulation) is fed as a cor-
recting variable to the pump.
The PWM signal generator gives the pump a periodic
sequence of impulses (the duty cycle) in accordance
with DIN IEC 60469-1.
Q/m³/ h
iPWM 1 mode (heating application):
In iPWM 1 mode, the pump speed is controlled according
to the PWM input signal.
Behaviour in the event of a cable break:
If the signal cable is disconnected from the pump,
PWM
100
%
e.g. due to a cable break, the pump accelerates to maxi-
mum speed.
PWM signal input [%]
< 5:
Pump runs at maximum speed
5-85:
The speed of the pump decreases linearly
from n
85-93: Pump runs at minimum speed (operation)
85-88: Pump runs at minimum speed (starting)
93-100: Pump stops (standby)
to n
max
min
Wilo SE 02/2018

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Para.../lin seriePara.../ipwm serie