Herunterladen Inhalt Inhalt Diese Seite drucken

Honeywell D15S Einbauanleitung Seite 6

Vorschau ausblenden Andere Handbücher für D15S:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
1. Safety Guidelines
1. Follow the installation instructions.
2. Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3. Note that the appliance is exclusively for use in the appli-
cations detailed in these installation instructions. Any
other use will not be considered to comply with require-
ments and would invalidate the warranty.
4. Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried out by
authorized persons.
5. Immediately rectify any malfunctions which may influence
safety.
2. Description of function
Spring loaded pressure reducing valves operate by means of
a force equalising system. The force of a diaphragm operates
against the force of an adjustment spring. If the outlet pres-
sure and therefore diaphragm force fall because water is
drawn, the then greater force of the spring causes the valve
to open. The outlet pressure then increases until the forces
between the diaphragm and the spring are equal again.
The inlet pressure has no influence in either opening or
closing of the valve. Because of this, inlet pressure fluctuation
does not influence the outlet pressure, thus providing inlet
pressure balancing.
3. Application
Medium
Drinking water, compressed air
ISO 8573-1 class 2 in consideration of
valid standards (e.g. EN 12502)
Inlet pressure
max. 16 bar
Outlet pressure
D15S / D15SI
1.5-6.0 bar (bis DN100)
D15S
1.5-8.0 bar (DN150 und DN200)
D15SN
0.5-2.0 bar
*
As part of an installation being approved according to PED
requirements, this product must also be certified.
4. Technical data
Operating
max. 65 °C
temperature
Nominal pressure
PN16
Minimum pressure
1.0 bar
drop
Nominal size
D15S
DN65, DN80, DN100, DN150, DN200
D15SN / D15SI
DN65, DN80, DN100
MU1H-1049GE23 R1215
GB
5. Scope of Delivery
The pressure reducing valve comprises:
• Housing flanges PN 16, ISO 7005-2, EN 1092-2, face to
face length acc. EN 558-1
• Spring bonnet with adjustment screw
• Adjustment spring
• Cartridge insert
• Pressure gauge
6. Options
D15S-... A = Standard version
D15SN-... A = Low pressure version
D15SI-... A = Stainless steel version
Connection size
acc.
*
7. Assembly
7.1. Installations Guidelines
• Install in horizontal pipework with spring bonnet directed
upwards
• Install shutoff valves
• The installation location should be protected against frost
and be easily accessible
- Pressure gauge can be read off easily
- Simplified maintenance and cleaning
• Install downstream of the filter or strainer
- This position ensures optimum protection for the pres-
sure reducing valve against dirt
• Provide a straight section of pipework of at least five times
the nominal valve size after the pressure reducing valve (in
accordance with DIN EN806 part 2)
7.2. Assembly instructions
1. Thoroughly flush pipework
2. Install pressure reducing valve
• Note flow direction
• Install without tension or bending stresses
3. Seal pressure gauge
6
Housing made from ductile cast iron (EN-GJS-
400-15 EN1563), coated with PA (polyamide)
DN65 - DN100 cartridge insert made low-lead
brass (< 2.2 % i.a.w. DIN 50930, Part 6) with
stainless steel valve spindle
DN150 - DN200 cartridge insert made from
stainless steel
Housing made from ductile cast iron (EN-GJS-
400-15 EN1563), coated with PA (polyamide)
Cartridge insert made from low-lead brass
(< 2.2 % i.a.w. DIN 50930, Part 6) with stainless
steel valve
Housing made from ductile cast iron (EN-GJS-
400-15 EN1563), coated with PA (polyamide)
Cartridge insert made from stainless steel
Special Versions available on request
Honeywell GmbH

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

D15snD15si

Inhaltsverzeichnis