Safety Relay

Operating Instructions
Read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before
working on this device.
CAUTION
Reliable functioning of the equipment is only ensured with certified
components.
The devices must be installed in switchgear cabinets with an adequate
degree of protection which takes the ambient conditions into account
IMPORTANT NOTICE
The products described herein are designed to be components of a customized machinery
safety-oriented control system. A complete safety-oriented system may include safety sen-
sors, evaluators, actuators and signaling components. It is the responsibility of each com-
pany to conduct its own evalution of the effectiveness of the safety system by trained
individuals. ABB AG, its subsidiaries and affiliates (collectively "ABB") are not in a position
to evaluate all of the characteristics of a given machine or product or machine not designed
by ABB.
ABB accepts no liability for any recommendation that may be implied or stated herein. The
warranty contained in the contract of sale by ABB is the sole warranty of ABB. Any state-
ments contained herein do not create new warranties or modify existing ones.
Application
You can use the safety relay C574 in EMERGENCY STOP devices as per
DIN EN / IEC 60947-5-5, in safety circuits as per and/or DIN EN / IEC 60 204-1, such as for
monitoring safety guards, or in circuits with controlled standstill requirement (STOP Cate-
gory 1). Depending on the external wiring max. Performance Level PL e / Cat. 4 / SIL 3 can
be achieved with this device for instanteneous enabling circuits and max. Performance
Level PL d / Cat. 3 / SIL 2 for time-delayed enabling circuits (according to
DIN EN ISO 13849-1 / DIN EN / IEC 62061). Der Anwender muss eine Bewertung des
Gesamtsystems durchführen.
Functions and connections
The C574 safety relay possess two delayed and two instantaneous release circuits as NO
circuits and one instantaneous signal circuit as NC circuit. Five LEDs indicate the operating
status and the functions.
The internal redundant safety relays, the electronics and the operated motor contactors are
tested for proper functioning when the EMERGENCY STOP button or the limit switch button
is unlatched, and when ON circuit Y33, Y34 is closed.
On the C574 (monitored start), the ON circuit Y33, Y34 is checked for short-circuit. This
means that a fault ist detected when Y33, Y34 is closed before the EMERGENCY STOP
button is closed.
Terminal
Operating voltage
assignments
The PE terminal should only be
connected if ground fault monitoring is
required.
Output
Monitored start Monitored start /
Function
ON
pushbutton at
1-channel
Y33, Y34
2-channel
2
Cable lengths
for 2 x 1.5 mm
Figures
Fig. I:
Dimension drawings (dimensions in mm)
Fig. II:
Installation / Cage Clamp
Fig. IIIa:
Safety data
Fig. IIIb:
Application data
Internal circuit: ¿ power pack, À PTC fuse, Á control logi, Â Channel 1,
Fig. IV:
à Channel 2, Ä Channel 1 (t), Å Channel 2 (t)
C574, Monitored start for EMERGENCY STOP
2
A1
L / +
A2
N / –
PE
Follow connection
notes given in Fig. VIII!
13, 14
Release circuit 1, instantaneous
23, 24
Release circuit 2, instantaneous
31, 32
Signal circuit, instantaneous
47, 48
Release circuit 1, delayed (t)
57, 58
Release circuit 2, delayed (t)
Autostart
Autostart
Jumper from Y11 to Y12
Feedback circuit or
Jumper from Y21 to Y22
Jumper to Y33, Y34.
EMERGENCY OFF circuit at Y10,
Y11
Jumper from Y10 to Y11
EMERGENCY OFF circuits at
Y11, Y12 and Y21, Y22
max. 1000 m (total length for sensors)
Order No.: 2CDC 113 019 M9701
Fig. V:
single-channel
Fig. VI:
two-channel
C574, Autostart for Guard door monitoring
Fig. VII:
single-channel
Fig. VIII:
two-channel
Operation
LEDs
POWER Ch1 Ch2 Ch1
(t)
.
Technical data
Permissible ambient temperature T
Operation / storage
Degree of protection to DIN EN / IEC 60529
Rated insulation voltage U
i
Rated impulse withstand voltage U
Rated control supply voltage U
Rated power
AC / DC operating range
Shock resistance
Weight
Recovery time after
EMERGENCY STOP
Release time after EMERGENCY STOP
Response time
Utilization category
as per
DIN EN / IEC 60947-5-1
AC-15
DC-13
Continuous current I
th
Short-circuit
Fuse links
protection
for release circuit
Duty class
and signal circuit
Duty class
for enabling circuits
Please adhere to the respective user information!
and signaling circuits
(Order No.: C98130-A7524-A1-05-7419)
Be sure to fit the specified fuses. Otherwise safe interruption in the event
of a fault cannot be guaranteed.
For further data and accessories see Catalog.
DIN EN / IEC 60947-5-1
Operation
Ch2
PS
EMERGENCY
ON
(t)
STOP
ON not activated
was activated closed
activated, delay
not activated open
time elapsed
not activated
not activated open
activated, delay
not activated FK 1 & 2 open,
time elapsed
Faults
• Relay fusion-welded
• Motor contactor fusion-welded
• Defect in electronics
• Short-circuit in ON circuit
Cross or ground faults in
EMERGENCY STOP circuit (min. fault
current I
= 0.5 A; PTC fuse trips)
Kmin
or supply voltage missing.
u
–25 to +60 °C / –40 to +80 °C
IP20
300 V
4 kV
imp
24 V DC, 24 V AC, 115 V AC, 230 V AC
s
3 W / 4 VA
0.85 to 1.1 x U
s
8 g / 10 ms
0.580 kg
Restart only possible after this time
elapses!
0.05 to 3 s or 0.5 to 30 s adjustable
max. 80 ms
Rated operational
Rated operational current I
voltage U
on loading of instantaneous / delayed
e
(V)
release circuits (A)
60 °C
70 °C
230
5 / 3
4 / 3
24
5 / 2
4 / 2
115
0.2 / 0.2
0.2 / 0.2
230
0.1 / 0.1
0.1 / 0.1
5 / 5
4 / 4
DIAZED
gL (gG) 6 A / quick response 10 A
gL (gG) 6 A / quick response 6 A
C574
English
Release circuits
FK 1 (t) &
FK 2 (t) closed
open
e