Mapping: Direct → Direct - Siemens ACP 1703 SM-x551/RP5ZA1 Handbuch

Inhaltsverzeichnis

Werbung

4.4.2.2. Mapping: Direct → → → → Direct
Application function of
Controlling Station
SELECT setpoint command
SELECT setpoint confirmation
DEACTIVATE setpoint
command
DEACTIVATE setpoint
confirmation
EXECUTE setpoint command
EXECUTE setpoint
confirmation
EXECUTE setpoint
termination
return step position
information
EXECUTE setpoint
termination
ACP 1703 Ax 1703, Systemelement-Handbuch SM-x551/RP5ZA1
DC0-077-2.00, Ausgabedatum 07.2009
Communication
services
<TI=48,49,50>,
COT=6, SE=1
<TI=48,49,50>,
COT=7, SE=1
„ACTCON negative"
<TI=48,49,50>,
COT=8, SE=x
<TI=48,49,50>,
COT=9, SE=x
„ACTCON negative"
<TI=48,49,50>,
COT=6, SE=0
<TI=48,49,50>,
COT=7, SE=0
<TI=48,49,50>,COT=10,
SE=0
<TI=48,49,50>,COT=10,
SE=0
1
If no return step position information is assigned to the setpoint - ACTTERM will be simulated directly after ACTCON
Communication
RP5ZA1
services
<SPM, FC=1>
<GOM, FC=11>
<EXR, FC=03> or
<NXR, FC=04>
1
Protokollbeschreibung
RTU-ABB
SETPOINT MESSAGE
GENERAL OUTPUT
MESSAGE
EXECUTED RESPONSE
or NOT EXECUTED
RESPONSE
return step position
information
63