FCOM
No.
14
15
16
17
18
19
20
21
22
23
ACP 1703 Ax 1703, Systemelement-Handbuch SM-x551/RP5ZA1
DC0-077-2.00, Ausgabedatum 07.2009
Meaning
Status check on satellite
Connect/disconnect mobile radio
connection
Generate an event message with line
statistics
Repeat all pulse counter values from
an end of period interval earlier than
given time. Day 0 means repeat all
stored counters.
Deactivate RTU
Accept a complete set of FTAB's
Database version
Switch main line
Enable/disable automatic switching
Setting summer time and normal
time. This command is sent twice
with different time settings.
Set Primary Mode
Additional Info
--
INFO1 = 1 = Connect
2 = Disconnect
INFO2 = Line number
INFO1 = Line number
INFO1 – INFO2 = DAY since 800101
INFO3 – INFO6 = Time in 0.1 ms since midnight
--
INFO1 – INFO2 = Days since 800101
INFO3 – INFO6 = Time in 0.1 ms since midnight
INFO1 = 0 = switch to A
1 = switch to B
INFO1 = 0 = enable automatic switching
1 = disable automatic switching
INFO1 – INFO2 = DAY since 800101
INFO3 – INFO4 = Time in minutes since
midnight
INFO5 – INFO6 = Offset to adjust in minutes.
Stated as 2´ compl.
INFO1 = 1 = Set primary mode
2 = Report current state no change
Protokollbeschreibung