Protokollbeschreibung
4.4.1.2. Mapping: Select Execute → → → → Select Execute
Application function of
Controlling Station
SELECT command
SELECT confirmation
DEACTIVATE command
DEACTIVATE confirmation
EXECUTE command
EXECUTE confirmation
EXECUTE termination
return indication
EXECUTE termination
58
Communication
RP5ZA1
services
<TI=45,46,47>,COT=6, SE=1
<TI=45,46,47>,COT=7, SE=1
<TI=45,46,47>,COT=8, SE=x
<TI=45,46,47>,COT=9, SE=x
<TI=45,46,47>,COT=6, SE=0
<TI=45,46,47>,COT=7, SE=0
<TI=45,46,47>,COT=10,
SE=0
<TI=45,46,47>,COT=10,
SE=0
1
If no return indication is assigned to the command - ACTTERM will be simulated directly after ACTCON
ACP 1703 Ax 1703, Systemelement-Handbuch SM-x551/RP5ZA1
Communication
services
CHECK BACK BEFORE
<CBXC, FC=5>
EXECUTE COMMAND
CHECK BACK RESPONSE
<CBR, FC=10> or
<NXR, FC=04>
<IHC, FC=3>
<EXR, FC=3> or
<NXR, FC=04>
<EXC, FC=13>
EXECUTE COMMAND
EXECUTED RESPONSE
<EXR, FC=03> or
<NXR, FC=04>
1
Ausgabedatum 07.2009, DC0-077-2.00
RTU-ABB
or
NOT EXECUTED
RESPONSE
INHIBIT COMMAND
EXECUTED
RESPONSE or
NOT EXECUTED
RESPONSE
or
NOT EXECUTED
RESPONSE
return indication