Liquipoint FTW33
The measuring device is shipped with "Standard" as the default setting. Optionally, it can be
ordered with "Extended" as the default setting, see order code on the nameplate: FTW33-
****HD****.
Standard: The green LED is continuously lit when the device is started.
Extended: The green LED flashes for approx. 5 seconds when the device is started and is then
continuously lit.
7.3.1
Switching between the Standard and Extended settings
The test magnet is included in the scope of delivery.
A: Hold the test magnet against the marking on the housing.
Start the device (operating voltage applied, voltage restored).
B: After at least 10 seconds, the measuring device has switched to Standard or Extended
mode.
Without LEDs: After at least 15 seconds.
C: After at least 30 seconds, the measuring device has reset to the default value.
Without LEDs: After at least 35 seconds.
gn
4
1
2
3
 13
Time diagram for settings and default value
7.4

Function test

WARNING
L
Risk of injury!
Ensure that no uncontrolled processes are activated in the system.
Carry out a function test while the device is in operation.
Hold the test magnet against the marking on the housing for at least 2 seconds.
 This inverts the current switch status, and the yellow LED changes state. When the
magnet is removed, the switching status valid at that time is adopted.
If the test magnet is held against the marking for longer than 30 seconds, the red LED will
flash: The device returns automatically to the current switch status.
Endress+Hauser
rd/gn
A
0
10
gn
rd/gn
B
25
Commissioning
gn
C
30
t/s
A0026044
39