Herunterladen Inhalt Inhalt Diese Seite drucken

Device Parameters And Information - thyracont VSP63E Betriebsanleitung

Vakuum transmitter
Vorschau ausblenden Andere Handbücher für VSP63E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

35
5.4

Device Parameters And Information

Type of Device TD:
Query of device type, e.g. VSP206
Product Name PN:*
Query of product name, e.g. VSP63E
Serial Number Device SD:*
Query of device serial number
Serial Number Head SH:*
Query of sensor head serial number
Version Device VD:*
Query of the device's hardware version
Version Firmware VF:*
Query of the device's firmware version
Version Bootloader VB:*
Query of the device's bootloader version
Baud Rate BR:*
Set the baud rate for RS485 data transmission
Value range: 9600, 14400, 19200, 28800, 38400, 57600, 115200 Bd
Response Delay RD:*
Query and set the time delay between receiving a telegram and sending the an-
swer.
Value range: 1 ... 99999 µs (default 5500 µs)
Device Restart DR:*
Make a device reset
*) Not accessible via EtherCAT