Herunterladen Inhalt Inhalt Diese Seite drucken

Fm / Csa - ABB TZIDC Betriebsanleitung

Vorschau ausblenden Andere Handbücher für TZIDC:
Inhaltsverzeichnis

Werbung

20
TZIDC, TZIDC-110, TZIDC-120 DIGITALER STELLUNGSREGLER | 42/18-84-DE REV. F
... 2 Einsatz in explosionsgefährdeten Bereichen
... TZIDC-120 – Ex-relevante technische Daten

FM / CSA

CSA International
Certificate
Certificate
Class 2258 04
Class 2258 02
Electrical data
Model TZIDC-120, P/N V18347-x042x2xx0x Intelligent Positioner
For use in
Input rated
Intrinsically safe with entity parameters of:
Terminals 11 / 12
Terminals 85 / 86
Terminals 41 / 42
Terminals 51 / 52
When installed per installation Drawing No 901265
Temperature Code
Max. Ambient temperature
Note
The „x" in P/N denotes minor mechanical variations or
optional features.
Local communication interface LCI shall not be used in
hazardous location.
Each pair of conductors of each intrinsic safety circuit shall
be shielded.
1649904 (LR 20312)
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For
Hazardous Locations
PROCESS CONTROL EQUIPMENT – For
Hazardous Locations
Class I, Div 2, Groups A, B, C and D;
Class II, Div 2, Groups E, F, and G,
Class III, Enclosure Type 4X
32 V DC; max.15 mA
(powered by a SELV circuit)
U max = 24 V
C
= 2,8 nF
i
I max = 250 mA
L
= 7,2 uH
i
U max = 30 V
C
= 3,8 nF
i
I max = 50 mA
L
= 0 uH
i
U max = 16 V
C
= 60 nF
i
I max = 20 mA
L
= 100 uH
i
U max = 16 V
C
= 60 nF
i
I max = 20 mA
L
= 100 uH
i
CSA certification record
Certificate
Certificate
Class 2258 04
Electrical data
Model TZIDC-120, P/N V18347-x042x2xx0x Intelligent Positioner
For use in
Input rated
Intrinsically safe with entity parameters of:
Terminals 11 / 12
Terminals 85 / 86
Terminals 41 / 42
When installed per installation Drawing No 901265
Temperature Code
Max. Ambient temperature
Note
The „x" in P/N denotes minor mechanical variations or
optional features.
Local communication interface LCI shall not be used in
hazardous location.
T4
Each pair of conductors of each intrinsic safety circuit shall
85 °C
be shielded.
1649904 (LR 20312)
PROCESS CONTROL EQUIPMENT – Intrinsically
Safe, Entity – For Hazardous Locations
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X
32 V DC; max. 15 mA
(powered by a SELV Circuit)
U max = 24 V
I max = 250 mA
U max = 30 V
I max = 50 mA
U max = 16 V
I max = 20 mA
C
= 2,8 nF
i
L
= 7,2 uH
i
C
= 3,8 nF
i
L
= 0 uH
i
C
= 60 nF
i
L
= 100 uH
i
T4
85 °C

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Tzidc-110Tzidc-120

Inhaltsverzeichnis