SIMEAS-T - Transducer with Auxiliary Power
Safety
according to DIN EN 600 part
overvoltage category
pollution degree
fire resistance class
safely seperated
dielectric strength (test voltage)
for type testing
– input - output
– input - auxiliary power
– output - auxiliary power
electromagnetic compatibility
interference radiation according to
– EN 5008-
– radio interference fields according
to EN 550
– radio interference voltage according
to EN 550
interference immunity according to
EN 5008-
• immunity to electromagnetic fields
according to
EN6000-4-3 (IEC 80-3)
• electrostatic discharge ESD according
to EN6000-4- (IEC 80-)
• fast transients, asymmetrical burst
according to EN6000-4-4 (IEC 80-4)
input and output
power supply
• surge according to IEC 80-5
• HF exposure according to IEC 80-6
3
III
V0
U
= 5.5 kV, 50 Hz, sine
eff
U
= 5.5 kV, 50 Hz, sine
eff
U
= 3.7 kV, 50 Hz, sine
eff
class B
class B
10 V/m
8 kV
kV
4 kV
0 V
rms