| Accessories
3. Activate the actuator. Go to Components menu, select Cooler menu and select type as Water. Choose actuator
voltage type. Do advanced settings if necessary.
4. Configure control signal to the actuator. Go to Service menu. Select Output menu. In next menu select ANALOG
tab. Select the analog output to which the control wire of the actuator is connected. Example if it is connected to AO3
on the connection board, then select ANALOG OUTPUT 3 and select Y3 Cooling from the output type list.
5. Since a duct temperature sensor replaces internal supply air temperature sensor, it doesn't need to be re-configured.
Note:
A duct temperature sensor can be connected to analog inputs 6–7 on the connection board for better
access and then configured as a supply air temperature sensor. However the internal supply air
temperature sensor must be disabled in the control panel first.
6. Duct cooler and its components are now configured.
11.3.4

Change-over coil for heating/cooling function

Change-over coil can be used for both heating and cooling based on the demand.
Important
The change-over (heating/cooling) system can be implemented in many different ways and may vary in
each household. This description explains the most common solution for connecting and controlling heating
and cooling with a water coil and a heat pump. Please always check with your local "Systemair" consultant if
your different solution for change-over function is supported by SAVE units.
• WH/WC — change-over coil
• FPT — frost protection sensor
(optional)
• SAT — supply air temperature sensor
• THS — thermostat for sensing if the
temperature of heating/cooling fluid
in the system is right (optional)
• HP — heat pump (or other device for
heating and cooling)
• CWP — water pump
• RL — relay
• 1 — Outdoor air
• 2 — Supply air
• 3 — Extract air
• 4 — Exhaust air
Component/product — Article number:
• Relay 24V with socket — 211248
• Duct sensor -30-70C (SAT) — 211524
• Surface sensor -30-150C (FPT) — 211523
Installation and connection
1. Install change–over coil in the duct. Install a water pump if necessary. The turning on and off of water pump should
be controlled with a relay (RL). Connect the relay to any free digital output and 24 V on the connection board. Then
connect the power supply and a water pump (CWP) to the relay.
2. Connect a control signal wire (if available) of the heat pump (HP) to any free digital output and 24 V on the connec-
tion board.
3. Connect cooling and heating start signal wires to any free digital outputs on the connection box. Relays (RL) must be
used.
4. The frost protection sensor (FPT) should be strapped on a surface on the return water pipe. Connect the frost protec-
tion sensor (FPT) sensor to any free analog input.