| Accessories

11.3 Temperature control

11.3.1

Electrical duct pre-heater

Electrical pre-heater can be installed in the outdoor air duct to pre-heat outdoor air before it reaches the unit and pre-
vent icing in the heat exchanger.
• PH — electrical pre-heater
• ECT — extra controller temperature sensor
• OAT — outdoor air duct temperature sensor
• RL — relay
• 1 — Outdoor air
• 2 — Supply air
• 3 — Extract air
• 4 — Exhaust air
Component/product — Article number:
• Duct temperature sensor (ECT) — 211524
• CB Preheater Connection Kit — 142852
• VSR 300:
CB 160-1,2 230V/1 Duct heater — 5291
• VSR 500:
CB 200-2,1 230V/1 Duct heater — 5384
Installation and connection
1. Install electrical pre-heater (ELH) at least 100 mm distance from the unit in the outdoor air duct. Relay (RL) is used to
control the pre-heater. Connect the relay to any free digital output on the connection board (CB).
2. Connect pre-heater (ELH) and the power supply to the relay (RL). A circuit breaker (BRK) is not included in the pack-
age and must be ordered separately. It must be installed in the circuit.
3. Install a duct temperature sensor (OAT) before the electrical pre-heater on the outdoor side of the unit and connect it
to any free Analog Input on the connection board (CB).
Fig. 13 Pre-heater connections
GB
211458 | A004