Herunterladen Inhalt Inhalt Diese Seite drucken

Installation Of Options - Siemens SIPART PS2 6DR50x0 serie Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4

Installation of Options

(see Figure 9, page 97)
Unscrew housing cover.
-
Unscrew module cover (1).
-
J
module: Insert the J
-
y
connection with the accompanying ribbon cable (6).
Alarm module: Insert the alarm module (4) into the upper PCB slot guide of the container, make the electrical
-
connection with the accompanying ribbon cable (5).
SIA module (slot-type initiator alarm module)
-
1.
Remove all electrical connections of the basic electronics (2).
2.
Loosen the two fixing screws (2.1) of the basic electronics.
3.
Unclip the basic electronics by carefully bending out from the four attachment points.
4.
Guide the SIA module (7) from above until the upper PCB slot guide of the container is reached.
5.
Push the SIA module approx. 3 mm to the right into the PCB slot guide of the container.
6.
Screw in the special screw (7.1) through the SIA module into the shaft of the positioner (Torque: 2 Nm)
CAUTION
!
The pins pushed into the control-gate valve bearing must be aligned shortly before contact with the
special screw. When screwing-in further, the control-gate valve bearing and the special screw must
be turned simultaneously so that the pins insert into the special screw. The SIA module may be da-
maged if you will not observe this.
7.
Place the insulation cover (10) over the SIA module on one side under the seating area of the basic
electronics on the container wall. The openings on the insulation cover must fit onto the corresponding
studs on the container wall. By carefully bending the container walls, fit the insulation cover over the
SIA module.
8.
Clip the basic electronics into the four attachment points and screw down the basic electronics with the
two fixing screws (2.1).
9.
Make all the electrical connections between the basic electronics and options with the accompanying
ribbon cables and between the basic electronics and the potentiometer with the potentiometer cable.
10. Attach the supplied module cover instead of the standard cover with the two screws.
11. Select the plates from the accompanying set of plates to correspond with those that were already
present on the standard version of the module cover. Stick the selected plates onto the mounted module
cover in accordance with the standard version.
12. Make all the electrical connections.
Setting the two limits:
13. Move the actuator to the first desired mechanical position.
14. Adjust the upper adjustment screw (for output terminals 41, 42) by hand until the output level changes.
15. Move the actuator to the second desired mechanical position.
16. Adjust the lower adjustment screw (for output terminals 51, 52) by hand until the output level changes.
.
NOTE
By rotating the adjustment screw past the level--changed value to the next level-changed value, you
can set a High-Low or a Low-High switch.
SIPART PS2
A5E00074600-05
module (3) into the lower PCB slot guide of the container, make the electrical
y
Operating instructions
53

Quicklinks ausblenden: