Herunterladen Inhalt Inhalt Diese Seite drucken

Preparation For Rotary Actuators - Siemens SIPART PS2 6DR50x0 serie Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

In the first line, the determined stroke in mm will appear in additional if the set lever length has been entered
with the parameter 3.YWAY.
After briefly pressing the mode key
are now in Configuration mode once more.
To leave Configuration mode, press the mode key
version will be displayed. After releasing the mode key, the device will be in Manual mode.
7.2

Preparation for rotary actuators

.
NOTE
Especially important: Switch the leverage ratio switch (7, leaflet "Operation -- a concise overview")
in the positioner into position 90° (usual adjustment angle for rotary actuators).
1.
Mount the positioner with the appropriate mounting kit (see Chapter 3.3, page 51).
2.
Connect the actuator and positioner with the pneumatic cables and supply pneumatic power to the positioner
(see Chapter 6, page 54).
3.
Connect a suitable current or voltage source (see Figure 10, page 98 to Figure 15, page 100).
4.
The positioner is now in "P manual" mode. On the upper line of the display, the current potentiometer voltage
(P) is displayed as a percentage, e.g. "P37.5", and on the lower line
"NOINI" is blinking:
5.
Check that the mechanism is able to move freely over the entire setting range by moving the actuator into
each final position with the
.
NOTE
You can move the actuator quickly by pressing the other direction key while you hold the first direc-
tion key down.
SIPART PS2
A5E00074600-05
, 5.INITM appears once more in the lower line. This means that you
for more than 5 s. After approx. 5 seconds, the software
and
keys.
Operating instructions
61

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis