Technical data

General information
Protection class to EN 60529
Weight
Dimensions L x W x H
Installation position
Directives
Low Voltage Directive
EMC Directive
Standards
Interference emission DIN EN 61000-6-3 (09/2011)
EN 61000-6-3 : 2007 + A1 2011
IEC 61000-6-3 + A1 2012
DIN EN 61326-6-1 (industry) (10/2006)
Interference resistance DIN EN 61000-6-2 (03/2006)
EN 61000-6-2 : 2005
IEC 61000-6-2 : 2005
DIN EN 61326-6-1 (industry) (7/2013)
Class
B
Group
1
Operating conditions
Ambient temperature
Storage temperature
Control medium
Dust content
Pressure dew point
Oil concentration
Air supply
Air consumption
Air output:
Electrical data
Power supply
Power supply
Power consumption
Input signals
Analogue inputs
Set values
Input resistance
Initialisation input (Digital)
Voltage
Level "Logical 1"
Level "Logical 0"
Input current
Analogue output
Actual value output
Load resistor
Electrical connection
Power supply
and signal connections
Positioner data
System deviation
Initialisation
Close tight function
Display elements
Status display
600 g
see pages 7 and 8
Optional
2014/35/EU
2014/30/EU
0 ... +60 °C
0 ... +60 °C
Quality classes to DIN ISO 8573-1
Class 7
(max. particle size 40 µm)
(max. particle density 5 mg/m³)
Class 4
(max. pressure dew point 3 °C)
Class 4
(max. oil concentration 5 mg/m³)
1.5 to 7 bar
0 l/min
(when idle)
150 l/min
U
= 24 V DC +10%/-5%
V
for flow rate code 01
I
= 100 mA (@ 24 V DC)
typ
4...20 mA
50
24 V DC
14 V DC ≤ U
≤ 30 V DC
H
0 V DC ≤ U
≤ 8 V DC
L
I
= 1.3 mA (at 24 V DC)
typ
4 - 20 mA
max. 600
1 x M12 plug (A-coded)
(Installation: Observe operating
instructions)
≤ 1%
Automatic via 24 V DC signal
CLOSED: W ≤ 0.5%;
OPEN: W ≥ 99.5%
4 LEDs
IP 65
100
75
50
25
0
0
4
0
During initialisation the GEMÜ 1436 cPos eco positioner
automatically detects the control function of the valve:
Normally open (NO) or Normally closed (NC)
For all valves the Closed position is at 4 mA.
Travel sensor
Linear design
Stroke
Resistance R
Minimum stroke
Quarter turn design
Angle of rotation
Resistance R
Materials
Housing cover
Housing base
43 / 56
Control diagram
5
10
15
8
12
16
2,5
5
7,5
integrated in directly mounted version
0 - 30 / 0 - 50 / 0 - 75 mm
3 / 5 / 5 k
≥ 1 mm
0 - 93°
3 k
PSU
PP30
1436 cPos eco
20
mA
20
mA
10
V

Werbung