7. Operating and setting
7.1 Configuration
This converter is composed of a two switches
block with two positions each (fig. 4 - item S ):
Switch 1
• The S S E E R R V V I I C C E E position is used to enter the para-
meters of the different modes.
• The O O P P E E R R A A T T I I O O N N position allows the selected
mode to run and hinders the access to parame-
ters input (normal operating).
Switch 2
• The position "key" is used to lock encoder.
• The position "no key" allows to use encode.
Example : Locking of set value in mode 1 or 2.
Fonctionnement de l' encodeur :
The selection of a new parameter is done only
with simple rotation.
" + " on right and " - " on left.
A short impulse on the encoder validates this
new setting.
7.1.1 Manual mode : MODE 1
When changing the motor speed with the enco-
der you reached the operating point.
Parameters input in Mode 1
If the pump is new and not integrated inside a
system, parameters are already in with operation
in Mode 1 ; (see § "Operation in Mode 1").
• Set the switch (fig. 4 - item. S) on position SER-
VICE.
• Sélect M1.
• Validate.
• Visualisation of the Operating time meter. (num-
ber of pump operating hours).
• Validate.
• Set the switch again on position OPERATION.
Operating in MODE 1
For the starting up, we recommend to set the
motor speed at 2000 (RPM).
When turning the encoder the requirement
value can be changed.
• Validate the new value.
With a short impulse on the encoder the actual
speed can be displayed ; after 30 seconds or a
new impulse the requirement value reappears.
An impulse around 1s allows the ON/OFF func-
tion).
• Sélect OFF.
• Validate.
Nota : the remote control (ex : switch) allows a
stop of the pump (converter ON).
When stopping the pump, the sign "OFF"
appears.
WILO AG 06/2008
ON
SERVICE
1
2
ON
1
2
MODE 1 - Manual mode
ON
SERVICE
1
2
MODE
Type
0,1s
Operation
hours
0,1s
ON
OPERATION
1
2
Set value
New
value
0,1s
1s
Actual
value
0,1s
ON
OFF
ON
OPERATION
1
2
ON
1
2
0,1s ou 1s
1s
0,1s