Line voltage faulty
Faulty connection
Broken motor winding Replace device
Deficient cooling
Ambient temperature
too high
Impermissible point of
operation (e.g. back
pressure too high)
In the event of further malfunctions, contact Systemair.
Operating instructions
Check line voltage,

6.1 Cleaning

restore power supply.
Attention! The error
message resets
automatically.
Device restarts
automatically without
warning.
Isolate from supply,
correct connection;

6.2 Safety inspection

see connection
diagram.
Improve cooling. Let
the device cool down.
To reset the error
message, switch off
the line voltage for at
least 25 s and then
switch it on again.
What to check How to check How often
Alternatively, reset
Contact
the error message by
protection
applying a control
cover for
signal of < 0.5 V to
intactness or
Din1 or by shorting
damage
Din1 to GND.
Device for
Reduce the ambient
damage to
temperature. Let the
blades and
device cool down.
housing
To reset the error
Fastening the
message, switch off
cables
the line voltage for at
Insulation of
least 25 s and then
cables for
switch it on again.
damage
Alternatively, reset
Tightness of
the error message by
cable gland
applying a control
signal of < 0.5 V to
Condensation
Din1 or by shorting
drainage holes
Din1 to GND.
for clogging,
Correct the operating
where necessary
point. Let the device
Welds for crack
cool down.
formation
To reset the error
message, switch off

6.3 Disposal

the line voltage for at
least 25 s and then
For Systemair, environmental protection and resource preservation are
switch it on again.
top priority corporate goals.
Alternatively, reset
the error message by
applying a control
signal of < 0.5 V to
Right from the development stage, ecological design, technical safety
Din1 or by shorting
and health protection are fixed criteria.
Din1 to GND.
The following section contains recommendations for ecological disposal
of the product and its components.
NOTE
Damage to the device during cleaning
Malfunction possible
→ Do not clean the device using a high-pressure cleaner.# Do
not use acid, alkali or solvent-based cleaning agents.
→ Do not use any pointed or sharp-edged objects for cleaning
NOTE
High-voltage test
The integrated EMC filter has Y capacitors. The tripping current
is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you perform the
legally required high-voltage test. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
What action?
Repair or
replacement of
device
Replacement of
device
Fasten
Replace cables
Retighten,
replace if
damaged
Open holes
Replace device