Technical information / Functioning / Parameters
Scaling the measuring
range
(analog output)
Voltage output
0 ... 10V
Current output
4 ... 20mA
Page 28
With the parameter "Lower end of analog output" (ASP) you can
select the measuring value for which the output signal is 4 mA or
0V. With the parameter "Upper end of analog output" (AEP) you
can select the measuring value for which the output signal is 20
mA or 10 V.
Minimum distance between ASP and AEP = 40 % of the final value of
the measuring range.
factory setting
U [V]
10
0
MEW = value of measuring range
The output signal is between 0 and 10V in the set measuring range.
It is also indicated:
Flow above the measuring range: output signal > 10V.
factory setting
I [mA]
20
4
0
MEW = value of measuring range
The output signal is between 4 and 20mA in the set measuring range.
It is also indicated:
Flow above the measuring range: output signal > 20mA..
U [V]
Q
MEW
I [mA]
Q
MEW
measuring range scaled
10
0
ASP
AEP
MEW
measuring range scaled
20
4
0
ASP
AEP
MEW
Q
Q