4.14

Connecting a voltmeter

The remote-connector offers a possibility to connect a voltmeter. It is possible to connect a
digital as well as an analogue voltmeter. This output can only be used when the voltage-
sense is connected. The voltage at this output is equal to the voltage measured at the point
where the voltage sense wires are connected.
Connecting a voltmeter
Disconnect the mains voltage.
Make sure that the voltage sense wires are connected, see chapter 4.8.
Connect a black wire between the "-" connection of the voltmeter and "-VM" at the
remote connector.
Connect a red wire between the "+" connection of the voltmeter and "+VM" at the
remote connector.
Connect the mains voltage.
4.15
Connecting a ampèremeter
The remote connector offers a possibility to connect an ampèremeter, which indicates the
output current of the charger. For the 50A charger an ampèremeter, which indicates 50A at
60mV input voltage is required. For the 80A charger an ampèremeter, which indicates
80A at 60mV input voltage is required, likewise for the 100A charger an ampèremeter,
which indicates 100A at 60mV input voltage is required.
Connecting an ampèremeter
Disconnect the mains voltage.
Connect a black wire between the "-" connection of the ampèremeter and "-AM" at
the remote connector.
Connect a red wire between the "+" connection of the ampèremeter and "+AM" at the
remote connector.
Connect the mains voltage.