BACnet Protocol Implementation Conformance
Statement (PICS)
Date: October 16, 2008
Vendor Name: ABB, Inc
Product Name: BACnet Router
Product Model Number: RBIP-01
Applications Software Version: 1.1
Product Description:
The ABB RBIP-01 snap-on module is a high-performance BACnet router for ABB standard drives for HVAC, ACH550.
This router supports 10/100 MBit/s BACnet/IP and BACnet over Ethernet networks, as well as BACnet MS/TP (EIA-485)
network.
The RBIP-01 router supports all standardized BACnet MS/TP baud rates up to 76.8k, as well as the master mode
functionality. BBMD (BACnet Broadcast Management Device) and FD (Foreign Device) functionalities are also supported.
The web server functionality enables access and configuration of the router using a standard web browser.
The RBIP-01 snap-on router is fully compatible with ABB standard drives for HVAC, ACH550, including older product
generations. The router fits inside the drive and does not affect the enclosure class of the drive. The router can be powered
from the drive or from an external power supply.
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building Blocks Supported (Annex K):
DS-RP-B
DS-RPM-B
DS-WP-B
DS-WPM-B
DM-DDB-B
DM-DOB-B
DM-DCC-B
DM-RD-B
Segmentation Capability:
Segmented requests supported
Segmented responses supported Window Size: 16
Standard Object Types Supported:
Object instantiation is static, i.e. objects cannot be created or deleted.
Refer to tables at end of this document for object details.
Data Link Layer Options:
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____________
BACnet Protocol Implementation Conformance Statement
Firmware Revision: 2.0
Data Sharing-ReadProperty-B
Data Sharing-ReadPropertyMultiple-B
Data Sharing-WriteProperty-B
Data Sharing-WritePropertyMultiple-B
Device Management-DynamicDeviceBinding-B
Device Management-DynamicObjectBinding-B
Device Management-DeviceCommunicationControl-B
Device Management-ReinitializeDevice-B
Window Size: 16