Herunterladen Inhalt Inhalt Diese Seite drucken

Legacy Whirlpool INT Enterprise SE Handbuch Seite 40

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

ELECTRICAL REQUIREMENTS
230 Volt 50 hz – residual current devices (rcds)
A residual current device (RCD, or R.C.D. henceforth) is the generic term for a device that monitors
the current in the line conductor and the neutral conductor in an earthed system.
In a circuit that's operating properly, the vector sum of the live and neutral current values added
together will be zero. Current flowing to earth, due to a line earth fault, will return via the earth
conductor, and regardless of load conditions, will be registered as a fault. This current flow will
give rise to a residual current that will be detected by the device. If the residual current exceeds the
rated sensitivity of the RCD, it will automatically activate a tripping of the faulty circuit.
Two Pole RCD
Total Ampere Rating
of Power System
0 A to 16 A
16 A to 20 A
20 A to 24 A
24 A to 28 A
28 A to 32 A
DO NOT DIVE.
DO NOT DIVE.
Four Pole RCD
Minimum Wire Size
Use Copper ONLY with 90˚C Insulation
#12 AWG / 3.31 mm
#10 AWG / 5.26 mm
#10 AWG / 5.26 mm
#8 AWG / 8.36 mm
#8 AWG / 8.36 mm
Typical specifications are as follows:
Residual Current Devices (RCDs) range
Sensitivity – from 10 to 500mA
Voltage – 2 poles: 230V; 3/4 poles:
230/400V
Connection capacity
- 25A: 6/10 mm
- 40,60A: 16/25 mm
- 80,100A: 35/50 mm
2
2
2
2
2
38
2
(flexible/rigid cable)
2
2
2
Ampere Rating of
RCD Circuit-Breaker
20
25
30
35
40

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Int inspire se

Inhaltsverzeichnis