For appliances containing FLAMMABLE REFRIGERANTS, ensure that
there are labels on the equipment stating the equipment contains
FLAMMABLE REFRIGERANT.
• Recovery:
When removing refrigerant from a system, either for servicing or
decommissioning, it is recommended good practice that all refrigerants are
removed safely.
• When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed. Ensure that the correct
number of cylinders for holding the total system charge is available. All
cylinders to be used are designated for the recovered refrigerant and
labelled for that refrigerant (i.e., special cylinders for the recovery of
refrigerant). Cylinders shall be complete with pressure-relief valve and
associated shut-off valves in good working order. Empty recovery cylinders
are evacuated and, if possible, cooled before recovery occurs.
• The recovery equipment shall be in good working order with a set of
instructions concerning the equipment that is at hand and shall be suitable
for the recovery of all appropriate refrigerants including, when applicable,
FLAMMABLE REFRIGERANTS. In addition, a set of calibrated weighing
scales shall be available and in good working order. Hoses shall be
complete with leakfree disconnect couplings and in good condition. Before
using the recovery machine, check that it is in satisfactory working order,
has been properly maintained and that any associated electrical
components are sealed to prevent ignition in the event of a refrigerant
release. Consult manufacturer if in doubt.
• The recovered refrigerant shall be returned to the refrigerant supplier in
the correct recovery cylinder, and the relevant waste transfer note
arranged. Do not mix refrigerants in recovery units and especially not in
cylinders.
• If compressors or compressor oils are to be removed, ensure that they
have been evacuated to an acceptable level to make certain that
FLAMMABLE REFRIGERANT does not remain within the lubricant. The
evacuation process shall be carried out prior to returning the compressor to
- 19 -