Checking the function
How to proceed:
1. If necessary, switch on the system and wait for 10 s until the control function is active.
2. Remove the shield from the probe.
3. Check the function:
– Remove all electrodes of the probe from the water. The valve opens after approx. 20 s. The
status LED lights up green on the controller.
– Immerse all electrodes of the probe in water. The valve closes after approx. 5 s. The status
LED of the controller extinguishes.
– If necessary, realign the probe.
4. Position the shield.
26
LEV0439