7.7.2 Digital input signals
Inputs:
Input voltage:
Logic level "1":
Logic level "0":
Input current:
7.7.3 Analogue output signals – Control module Positioner (code S0, S5, S6)
7.7.3.1 Actual value
Output signal:
Output type:
Accuracy:
Temperature drift:
Load resistor:
Resolution:
Short-circuit proof:
7.7.4 Digital output signals
Outputs:
Type of contact:
Switching voltage:
Switching current:
Short-circuit proof:
www.gemu-group.com
Function selectable via IO-Link (see table Overview of available functions – Input and output sig-
nals)
24 V DC
> 15.3 V DC
< 5.8 V DC
typically < 0.5 mA
0/4 - 20 mA; 0 - 10 V (function selectable via IO-Link)
Active
≤ ±1% of full flow
≤ ±0.1% / 10°K
≤ 750 kΩ
12 bit
Yes
Function selectable via IO-Link (see table Overview of available functions – Input and output sig-
nals)
Push-Pull
Power supply Uv
≤ 140 mA
Yes
65 / 108
7 Technical data
GEMÜ R563 eSyStep