Type C43
Gas appliance with combustion air inlet and exhaust system to be
connected to an exhaust system.
Type C53
Gas appliance with separate combustion air inlet and exhaust
system. The inlets are located in different pressure ranges.
Note: The chimney draught specifications given in the technical
data must be maintained if you want to achieve the prescribed
combustion values.
Drainage of condensate
The condensate pipes must be siphoned directly at the conden-
sate connection. The siphon height must be 30 cm. The siphon is
included in the scope of delivery. The condensate pipe must not
be firmly connected to the drainage system. The condensate
must first flow out freely into a funnel or a neutralisation container.
– Before installing, please check the load-bearing capacity of
the wall. The fastening material delivered with the plant is
suitable for concrete walls. Use suitable anchor plugs and
screws for hollow component walls, brick walls and gas con-
crete walls - for e.g. injection anchor (for drilling diagram see
the specifications sheet).
– Figure 3 - items 19 and 25
The appliance should not be directly attached to the network
of water and high pressure pipes. It is mandatory to install the
connecting hoses.
– Figure 3 - A
A shut-off tap must be installed between the main water sup-
ply and the connecting hose.
Installing the high pressure connections
All national laws and regulations about installation of electrical
appliances must also be followed when installing high pressure
lines.
– The pressure loss in the pipe connections must lie below 1.5
MPa.
– The completed pipe connections must be checked using 32
MPa.
– The insulation of the pipes must be resistant to temperatures
until 100 °C.
Install the detergent tank
Figure 3 - Pos. 20
The tanks are to be installed in such a way that the lower level
mirror of the detergent should not be more than 1.5 m under the
machine floor and the upper level mirror should not be located
above the machine floor.
Figure 3 - B and item 19
 The water inlet is to be connected to the main water supply
using an appropriate water hose.
– The water supply must have a minimum output of 1300 l/h at
minimum 0.1 MPa.
– The water temperature must lie below 30 °C.
15
-
EN

Wall mount

Water supply