5. Commissioning, operation
Connection terminals and wire preparation
EN
Types of single
conductors
Wire length
Maximum length of
the bare wire end
Number of wires /
Cross-sections
Recommended
tightening torque
5.2.4 Switch contacts
■
The position of the switch points and the switching functions are indicated on the
product label.
■
The assignment of the individual switching functions is marked on a sticker affixed to
the mating connector at the terminal:
Wiring scheme
First digit
Second digit
Wiring scheme
Wiring scheme
12 13 11 21 23 22 32 33 31 41 43 42
Terminal
Status of switching output: Not pressurised
14
Connection terminals of
the socket terminal strip
■
Solid wire core
■
Flexible strand
■
Flexible strand with end splice
≥ 90 mm
Max. 5.5 mm
1 x 0.5 mm² to 1 x 2.5 mm²
0.5 Nm
■
1x – Switch contact S1
■
2x – Switch contact S2
■
3x – Switch contact S3
■
4x – Switch contact S4
■
x1 – Common
■
x2 – Normally closed
■
x3 – Normally open
S1
Connection terminals of
the protective conductor
■
Solid wire core
■
Flexible strand with end splice
≥ 120 mm
Max. 8 mm
1.2 Nm
S2
S3
S4