Model
Maximum continuous output
current [A]
Power factor range
Maximum units per 10 AWG
branch²
Maximum units per 12 AWG
branch²
Current inrush [a.c. A]
Max output fault current [a.c. A]
Max output overcurrent protection
[a.c. A]
Total harmonic distortion [%]
Model
Rated output apparent power [VA]
Maximum continuous output power
[VA]
Nominal AC voltage [a.c. V]¹
Nominal AC frequency [Hz]¹
Maximum continuous output
current [A]
Power factor range
Maximum units per 10 AWG
branch²
Maximum units per 12 AWG
branch²
Current inrush [a.c. A]
Max output fault current [a.c. A]
Max output overcurrent protection
[a.c. A]
Total harmonic distortion [%]
68
X1-Micro 1300
5.91@220V
5.66@230V
5.42@240V
>0.99(-0.8~0.8 adjustable)
6@220V
7@230V
7@240V
5@220V
5@230V
5@240V
X1-Micro 1800
1800
1800
220 or 230 or 240 / 180-264
8.19@220V
7.83@230V
7.50@240V
>0.99(-0.8~0.8 adjustable)
4@220V
5@230V
5@240V
3@220V
4@230V
4@240V
X1-Micro 1500
6.82@220V
6.53@230V
6.25@240V
5@220V
6@230V
6@240V
4@220V
4@230V
5@240V
12
16
15
<3
X1-Micro 2000
2000
2000
50/60
9.10@220V
8.70@230V
8.34@240V
4@220V
4@230V
4@240V
3@220V
3@230V
3@240V
12
16
15
<3
X1-Micro 1600
7.28@220V
6.96@230V
6.67@240V
5@220V
5@230V
6@240V
4@220V
4@230V
4@240V
X1-Micro 2200
2200
2200
10.00@220V
9.57@230V
9.17@240V
4@220V
4@230V
4@240V
3@220V
3@230V
3@240V