6.9
Pressure tap piece
Verify that the pressure tap piece is mounted at a point with unobstructed
flow or steady measuring conditions.
Verify that the hole for the pressure tap piece is sufficiently large.
- Install a shut-off unit for the pressure tap.
6.10 Measuring line
The measuring line connects the pressure tap piece and the product.
Verify that the inside diameter of the measuring line is sufficiently large to
help avoid clogging.
Verify that the measuring line has a steady gradient.
- Provide a drain point at the lowest point in the case of gases and a vent
point at the highest point in the case of highly viscous liquids.
In the case of gases and liquids containing solid particles, verify that a
separator is installed which can be separated from the system by means
of a shut-off unit during operation for emptying.
Verify that the measuring line is installed in such a way that it can absorb
all loads and stresses caused by expansion, vibration or heat influences.
Mounting
RF ... EX / KP ... EX
EN