Room thermostat II 230  V
݃ When connecting the device terminals, ensure that permitted wires and
wire cross sections are used.
݃ The consumers connected to the relay outputs must have sufficient
insulation.
݃ Observe the technical data, in particular the maximum permissible
switching power of the relay and the type of consumer to be connected,
before connecting a consumer. The device
should only be loaded to the specified power limit. Overloading may
result in destruction of the device, fire or an electrical accident. Among
other things, reliable switching off of the connected consumer cannot be
guaranteed.
݃ The power circuit to which the device and the load are connected must
be secured with a circuit breaker in accordance with EN 60898-1 (trigger
characteristics B or C, max. 16 A rated current, min. 6 kA breaking
capacity, energy limitation class 3). Installation guidelines in accordance
with the applicable national standards, e.g. VDE 0100 or HD384 or IEC
60364, must be observed. The circuit breaker must be easily accessible
for the user and labelled as a disconnecter for the device.
݃ When using the device in wet rooms such as bathrooms, a minimum
distance of 60 cm from wet areas, such as a bathtub, shower or wash
basin must be maintained.

Installation and mounting

݃ Before you start: Be sure to shut off the power circuit breaker!
If necessary, remove an existing thermostat.
↑Contents
8-750-002-893 | V001 | 01/2024
English | 10