Herunterladen Diese Seite drucken

Elektro-Automatik PS 8160-05 2U Bedienungsanleitung Seite 30

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Operating the device
In memory selection mode the button is also used to switch to
the UVL or OVP value of the selected memory set, but in this
mode the values are not valid yet. The left display area will then
show like this:
resp.
Pushbutton Preset Power
During normal operation the button is used to switch the display
from actual current to preset value of the output power (preset
mode).
Models from 1kW feature an adjustable power regulation and will
show like this on the right display area:
In preset mode, the right rotary encoder (Current / Power) is used
to adjust the power set value from 0...100% P
value is instantly transferred to the output!
A second push exits the preset mode instantly or it is exited
automatically after 5s, if no preset button is pushed or any set
value is altered.
During remote control by analogue or digital interface the preset
mode can be used to check the power set value that is given
from remote.
The button may be locked by the condition LOCK. See below.
In memory selection mode the button is also used to switch to the
power set value (only models from 1kW) of the selected memory
set, but in this mode the set value is not transferred to the output.
The right display area will then show like this:
Pushbutton Preset Current
During normal operation the button is used to switch the display
from actual to preset value of the output current (preset mode).
Die Darstellung ändert sich rechts in:
In preset mode, the right rotary encoder (Current / Power) is
used to adjust the set value of current from 0...100% I
same way as in normal operation. The adjusted value is instantly
transferred to the output!
A second push exits the preset mode instantly or it is exited
automatically after 5s, if no preset button is pushed or any set
value is altered.
0
During remote control by analogue or digital interface the preset
mode can be used to check the current set value that is given
from remote.
The button may be locked by the condition LOCK. See below.
In memory selection mode the button is also used to switch to the
current set value of the selected memory set, but in this mode the
set value is not transferred to the output. The right display area
.
will then show like this:
Pushbutton Memory Select M1-M5
This button cycles through the 5 memory sets, each with set
values for U, I and P, as well as UVL and OVP. From here, the
selected memory set can be edited, stored or submitted. The
button only works if the output is off. The memory mode and the
selected memory set number are displayed like this:
. The adjusted
Nom
By using the button the user can:
a) Adjust values
Output off, short push of the button, the display changes to the
first memory set as displayed above.
Now the set values of U (left) and I (right) of the selected memory
set can be adjusted. The other adjustable values can be accessed
by pushing the corresponding preset buttons.
Further pushes will cycle through the memory sets up to number
5 and then exit memory mode.
The adjusted values remain as long the device is powered, but are
not submitted to the output set values and are not saved yet!
Pushbutton Memory Start / Memory Save >3s
This pushbutton is either used to submit the values of the memo-
ry set that has been selected before by button Memory Select
M1-M5 to the output or to save the memory to internal flash. The
button only works if the output is off.
By using the button the user can:
b) Submit only
Output off, memory set is selected (1-5), button is pushed shortly
--> the values of the memory set are submitted to the set values
of the output and the memory mode exits. In order to use the new
set values, the output is switched on as usual by button Output
On or by remote control.
Attention! Submitting the values does not save them!
the
c) Save only
Nom
Output off, select memory set(s), adjust the values as desired,
the push the button >3s --> all memory sets are saved to internal
flash, but none is submitted to the output. The output remains off,
the memory mode exits after saving.
© 2006, Elektro-Automatik GmbH & Co. KG
Irrtümer und Änderungen vorbehalten
© 2009, Elektro-Automatik GmbH & Co. KG
EN

Werbung

loading