Herunterladen Diese Seite drucken

Victron energy PIN483020000 Anleitung Seite 17

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 65
Setting ds2 and ds1 for stand-alone operation
DS-8 not used
DS-7 not used
DS-6 not used
DS-5 AES
DS-4 Inverter voltage
DS-3 Inverter frequency
DS-2 Stand-alone operation
DS-1 Stand-alone operation
Examples of DIP switch settings for stand-alone mode are given below.
Example 1 shows the factory setting (since factory settings are entered by computer,
all DIP switches of a new product are set to 'off').
Four examples of stand-alone settings:
DS-8 not used
DS-7 not used
DS-6 not used
DS-5 AES
DS-4 Inverter voltage
DS-3 Inverter frequency
DS-2 Stand-alone mode
DS-1 Stand-alone mode
stand-alone
Example 1 (factory setting):
5 AES: off
4 Inverter voltage 230V
3 Inverter frequency 50Hz
2, 1 Stand-alone mode
To store the settings after the required values have been set: press the 'Up' button for
2 seconds (upper button to the right of the DIP switches, see appendix A, position J).
The overload and low-battery LEDs will flash to indicate acceptance of the
settings.
You can leave the DIP switches in the selected positions, so that the settings can
always be recovered.
Set off
Set off
Set off
Set as desired
Set as desired
Set as desired
off
DS-8
off
DS-7
off
DS-6
off
DS-5
on
DS-4
on
DS-3
off
DS-2
off
DS-1
stand-alone
Example 2:
5 AES: off
4 240V
3 60Hz
2,1 Stand-alone
off
off
off
off
off
off
DS-8
off
off
DS-7
off
off
DS-6
off
off
DS-5
off
off
DS-4
on
off
DS-3
off
off
DS-2
off
off
DS-1
off
stand-alone
Example 3:
5 AES: off
4 230V
3 60Hz
2,1 Stand-alone
DS-8
off
DS-7
off
DS-6
off
DS-5
on
DS-4
off
DS-3
on
DS-2
off
DS-1
off
stand-alone
Example 4:
5 AES: on
4 240V
3 50Hz
2,1 Stand-alone
15

Werbung

loading