ATTENTION! Before further disassembly, it is absolutely necessary to relieve the pressure!
Pressure relief: According to chapter 7 „Setting output pressure", Fig. 7.2, minimise the
pressure (-) while observing the pressure gauge. To do this, turn the hexagonal pin spanner
anticlockwise as far as it will go.
Fig. 8.12: Turn the screw cap [a] in the direction
/
of the arrow using a pair of valve pliers and
remove it from the housing
During assembly, ensure that a tightening
torque of 25 Nm is observed.
Fig. 8.13: Remove adjusting screw unit [b] and
/
spring [c]
Place a slotted screwdriver in the notch of the
/
hexagon nut [d]
carefully lift or lever the unit upwards
/
Fig. 8.14: Remove cartridge [e] with the slide ring [f]
/
clean the cartridge [e] under clear, cold water,
/
replace if necessary (see chapter 11 Spare parts)
mount the CLEAR PRO RD domestic water
/
unit in reverse order and screw it to the flange
according to chapter 6.2
ATTENTION - DON'T FORGET:
/
After complete assembly, follow the instructions
in chapter 7, Setting the output pressure