INSTALLATION
Specification
If the flow rate is too low
f Unscrew the cap from the butterfly valve.
f Using a screwdriver, turn the butterfly valve adjusting screw
anti-clockwise to increase the flow rate.
f Measure the flow rate again.
f Adjust the flow rate with the butterfly valve, until the meas-
ured flow rate corresponds at most to the maximum permis-
sible flow rate.
f Screw the cap onto the butterfly valve.
www.stiebel-eltron.com
8.
Specification
8.1
Dimensions and connections
MEK-K
70(100)
198
288
100
G1/2
193