Outputs
Output relay
Switching capacity: max. 250V AC, 4 A. The current has to be limited to
these values by appropriate external measures. For inductive loads the relays
must be subjected to external interference suppression.
The relay contacts are safely separated from the supply voltages of the unit,
from the sensor and contacts of the second relay, if there is any, up to a
rated voltage of 250 V AC. They conform to the overvoltage category 2
and soiling degree 2.
NOTE: If the relay is used to switch very low currents (e.g. plc inputs),
considerable contact resistance can arise. The life of the relay contacts is
considerably reduced by excess current or by the switching of unprotected
inductive loads.
Transistor output (A 300 with AC/DC switched-mode power supply)
PNP, 24 V DC, ±20%, 700 mA, external supply at terminal 9. The voltage of
the short-circuit protected transistor output is switched to terminal 10
depending on the selected function. It is not allowed to apply external vol-
tage to terminals 10 and 11.
Unit data
Dimensions: 75 x 55 x 110 (H / W / D), weight: max. 400g
Protection rating housing: IP 40, protection rating terminals: IP 20
Connection: 16 terminals, wire cross section: max: 2.5mm
Environmental conditions
Permissible ambient temperature: -20°C...+60°C in open air
Humidity: max. 75% up to +35°C, non condensing
Air pressure: 75 KPa to 106 KPa
Maximum operating altitude: 2000m above sea level
CE marking
The unit has the CE mark which is necessary for the free exchange of good
within Europe. It shows that the unit meets the requirements according to
the accepted general protective purposes.
In particular it shows the conformity with the following guidelines:
• EMC guideline EMC 89/336/EEC,
stipulated in the standards EN 60947-5-2 annex X
(The user is responsible for the interference suppression of the relay circuit
according to the standard).
• Low voltage guideline LV 73/23/EEC,
stipulated in the standard EN61010:1993 + A2:1995
Other requirements, e.g. concerning the EC guideline for machines, are to
be considered by the user in his planned application and are not part of the
certificate of conformity.