7
ABB AC700
CCTW++++++++IMMMM+++
SDRAM Memory Test successful
Memory Map Done
AC700 Boot
Version 09.01.17
Press 2 to boot alternate OS
Uncompress OS
AC700F-OS Version 009 001 188
******************************************************************************************
Uncompress completed
Uncompress successful
S
ABB ** AC700F **
(C)2007 ABB Automation Products
------------------------------------------------------------------------------
CPU is MPC852T (96 MHz) with 8MB SDRAM, 2MB SRAM, 4MB Flash
System will start without debugger
Auto restore from SD card is disabled
OS trace is disabled
Coupler bus is enabled
Network Interface [00:C0:C9:1B:00:19] - 10 MBit half duplex
- IP address: 172.16.1.16
- Subnet mask: 255.255.240.0
RTC-Time: 22.07.08, 12:15:10 local
------------------------------------------------------------------------------
To change these parameters, hit <SPACE> within 2 seconds
Abb. 37
Systemmeldungen des Boot-Loaders bis zur Tastaturabfrage
Die Konfigurationsdaten des Boot-Loaders können Sie jederzeit aufrufen, indem Sie
während der Wartezeit von zwei Sekunden die Leertaste betätigen. Es erscheint dann
die folgende Meldung:
Enter PIN code: ****
<C>hange, set <T>ime or <P>in, <L>oad config, <S>ave or continue <B>ooting?
Die PIN-Abfrage erscheint nicht bei der Erstinbetriebnahme, sondern erst später,
nachdem diese Sicherheitsfunktion mit Hilfe des Terminalprogramms oder über das
Display des CPU-Moduls aktiviert wurde
Konfigurationsdaten
Im Unterpunkt <C>hange können Sie die Konfigurationsdaten des Controllers ändern.
Nach der Eingabe von C erscheint die folgende Anweisung:
For each of the following questions, hit <RET> to keep the value in braces or enter a new
value.
7-4
Date: Fri Jul 04 18:47:15 2008 by GEN , Buildindex 6986$
.
Inbetriebnahme
M&I – AC 700F Controller