Herunterladen Diese Seite drucken

AFRISO EURO-INDEX LAG-14 ER Betriebsanleitung Seite 86

Vorschau ausblenden Andere Handbücher für LAG-14 ER:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
5.8.2
Voltage-free changeover contact (relay output)
VOLTAGE PEAKS WHEN INDUCTIVE CONSUMERS ARE SWITCHED OFF
When inductive consumers are switched off, this can cause voltage peaks and
can lead to adverse effects on electrical systems and may destroy the switching
contact.
Use commercially available standard RC combinations such as 0.1
µF/100 Ohm for inductive consumers.
Failure to follow these instructions can result in equipment damage.
The output signal of the control unit is made available via a voltage-free
changeover contact (relay contact). The output signal of the product can
be transmitted to an additional alarm unit (for example, ZAG 01).
1. Replace the blind plug by a suitable cable gland.
- You can use, for example, the "Sealing kit IP 54" for cables with a diam-
eter of 5 ... 10 mm.
- The cable for the output signal must be routed separately.
2. Connect the additional equipment to the terminals "Alarm".
- Refer to the operating instructions of the manufacturer of the additional
equipment for further information.
Mounting
NOTICE
LAG-14 ER
EN
34

Werbung

loading