5
Mounting
5.1
Preparing mounting
5.1.1
Calculation base for tanks
The active volume of the leak detection fluid container is 4.5 litres. The
volume is limited by the liquid level screw in the centre of the container.
Refer to the nameplate at the tank for the interstitial space volume of the
tank.
The product can also be used for tanks with large interstitial space vol-
ume. For this purpose, additional containers with an active volume of
4.5 litres each must be used.
The additional containers are connected to the container for leak detec-
tion fluid by means of connection lines (EPDM).
The following applies to underground tanks:
• One litre of leak detection fluid is required in the container for leak
detection fluid per 100 litres of interstitial space volume.
The container for leak detection fluid is sufficient for 450 litres of interstitial
space volume.
Volume of leak detection
fluid [litres]
0 - 450
450 - 900
900 - 1350
1350-1800
1800 - 2250
Mounting
Container for leak
detection fluid (with
probe)
1
1
1
1
1
Required addi-
tional containers
(without probe)
0
1
2
3
4