4.6
Voltage-free changeover contact (relay output)
The control unit features a voltage-free changeover contact for transmission
of the alarm condition to additional equipment.
The product can be operated with or without additional equipment for trans-
mission of the alarm condition, for example:
Visual and audible alarm units
Remote alarm equipment
Building control systems
Other
Operating mode Eco
The product is factory-set to the operating mode "Eco". If no alarm is present,
the relay is de-energised. In case of an alarm, the relay is energised.
Operating mode Failsafe
You can also operate the product in the operating mode "FailSafe" (see "Set-
ting the operating mode"). If no alarm is present, the relay is energised. In the
case of an alarm, of a failure of the control unit, or of power outage, the relay
is de-energised.
4.7
Approvals, conformities, certifications
The product complies with:
EMC Directive (2014/30/EU)
Low Voltage Directive (2014/35/EU)
Construction Products Directive (EU) Nr. 305/2011 and no. 574/2014
(EN 13160-1:2003 and EN 13160-3:2003)
RoHS Directive (2011/65/EU)
ATEX Equipment Directive (2014/34/EU)
The markings of the component of this product are:
- Control unit:
- Container for leak detection fluid and probe: Ex ia IIB T6 Ga
Product description
II 1 G [Ex ia Ga] IIC
LAG-14 ER