5.8
Supply voltage
Verify that the product is connected to mains by means of a suitable,
permanently installed cable (for example, NYM-J 3 x 1.5 mm²).
Verify that the power supply to the control unit is separately fused (16 A
maximum).
1. Open the control unit.
2. Route the mains cable through the left cable gland into the control unit.
3. Connect the phase to terminal L and the neutral conductor to
terminal N.
- The protective ground conductor (PE) does not have to be connected.
A
Fig. 7: Electrical connection
Mounting
B
F
E
C
D
A. Mains fuse (F1)
B. Relay fuse (F2)
C. Jumper for operating
mode
D. Probe connection
E. Voltage-free changeover
contact
F. Connection terminal for
power supply
LAG-14 ER
EN
31