Herunterladen Diese Seite drucken

Toshiba RAV-SM560KRT-E Installations-Handbuch Seite 13

Vorschau ausblenden Andere Handbücher für RAV-SM560KRT-E:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 36
Packed valve handling precautions
• Open the valve stem all the way out ; do not try to
open it beyond the stopper.
• Securely tighten the valve stem cap in torque as
follows:
Gas side (12.7 mm (diam.))
Gas side (9.52 mm (diam.))
Liquid side (6.35 mm (diam.))
Service port
Hexagonal wrench is required.
<For RAV-SM800AT-E model>
• As shown in the figure, be sure to use a double
spanner to loosen or tighten the flare nut of the valve
at gas side. If using a single spanner, the nut cannot
be tightened with necessary tightening torque.
On the contrary, use a single spanner to loosen or
tighten the flare nut of the valve at liquid side.
Cap
Loosened
SM800 type valve at gas side
50 to 62 N•m (5.0 to 6.2 kgf•m)
33 to 42 N•m (3.3 to 4.2 kgf•m)
14 to 18 N•m (1.4 to 1.8 kgf•m)
14 to 18 N•m (1.4 to 1.8 kgf•m)
Cover
Piping valve
Tightened
Flare nut
Cover
Do not put the spanner or
torque wrench, etc. on
the cover.
The valve may be broken.
<For RAV-SM560AT-E model>
Compound pressure gauge
–101kPa
(–76cmHg)
Handle Lo
Charge hose
(For R410A only)
Packed valve (Gas side)
Service port (Valve core (Setting pin))
Valve unit
Charge port
<For RAV-SM800AT-E model>
Compound pressure gauge
–101kPa
(–76cmHg)
Handle Lo
Charge hose
(For R410A only)
Service port
(Valve core (Setting pin))
Packed valve at gas side
10
Pressure gauge
Manifold valve
Handle Hi
(Keep fully closed)
Charge hose
(For R410A only)
Vacuum pump adapter
for counter-flow prevention
(For R410A only)
Vacuum
pump
Flare nut
Stopper
Charge cap
Valve rod
Pressure gauge
Manifold valve
Handle Hi
(Keep fully closed)
Charge hose
(For R410A only)
Vacuum pump adapter
for counter-flow prevention
(For R410A only)
Vacuum
pump

Werbung

loading

Diese Anleitung auch für:

Rav-sm560at-eRav-sm800krt-eRav-sm800at-e