ELECTRICAL WIRING
!
C A U T I O N
Wrap the accessory packing around the wires, and plug the wiring
connection hole with the seal material to protect the product from any
condensate water or insects.
Tightly secure the wires with the cord clamp inside the indoor unit.
Lead the wires through the knockout hole in the side cover when
using conduit.
Secure the cable of the remote control switch using the cord clamp
inside the electrical box.
15.1 GENERAL CHECK
1 Make sure that the field-selected electrical components (main
power switches, circuit breakers, wires, conduit connectors
and wire terminals) have been properly selected according to
the electrical data given in "Technical Catalog". Make sure that
the components comply with National Electrical Code (NEC).
2 Use the shielded twist pair cable for the control cable between
the outdoor unit and the indoor unit, the control cable between
indoor units and the remote control switch cable.
15.2 ELECTRICAL WIRING CAPACITY
15.2.1 Field minimum wire sizes for power source
Do not operate the system until all the check points have been cleared.
a. Check to ensure that the electrical resistance is more
than 1 megohm, by measuring the resistance between
ground and the terminal of the electrical parts. If not,
do not operate the system until the electrical leakage is
found and repaired. Check to ensure that the stop valves
of the outdoor unit are fully opened, and then start the
system.
Model
RPC-(1.5-6.0)FSR
?
N O T E
Follow local codes and regulations when selecting field wires.
The wire sizes marked with *1 in the above table are selected at the
maximum current of the unit according to the European Standard,
EN 60335-1. Use the wires which are not lighter than the ordinary
tough rubber sheathed flexible cord (code designation 60245 IEC 57)
or ordinary polychloroprene sheathed flexible cord (code designation
60245 IEC 57).
Current i (A)
i < 6
6 < i < 10
10 < i < 16
16 < i < 25
25 < i < 32
32 < i < 40
40 < i < 63
63 < i
23
PMML0551 rev.1 - 02/2021 - A10762310A
Maximum
Power source
current
1~ 230V 50Hz
5A
Selection according to EN 60335-1
In the case that current exceeds 63A, do not connect cables in series.
?
N O T E
The procedure of the wiring work shall be performed according to this
manual and Installation and Operation Manual of the outdoor unit.
3 Check to ensure that the power supply voltage is within
±10% of the rated voltage.
4 Check the capacity of the electrical wires. If the power
source capacity is too low, the system cannot be started due
to the voltage drop.
5 Check to ensure that the earth wire is connected.
b. Check to ensure that the switch on the main power
source has been ON for more than 12 hours, to warm the
compressor oil by the crankcase heater.
Do not touch any of the parts by hand at the discharge gas
side, since the compressor chamber and the pipes at the
discharge side are heated higher than 90ºC.
Power source cable size
EN 60335-1 *1
0.75mm
2
Use a shielded cable for the transmitting circuit and connect it to
ground.
In the case that power cables are connected in series, add each unit
maximum current and select wires below.
Wire size (mm
)
2
0.75
1
1.5
2.5
4
6
10
Transmitting cable size
EN 60335-1 *1
0.75mm
2