Herunterladen Diese Seite drucken

Hitachi RPC-1.5FSR Installations- Und Betriebshandbuch Seite 61

Vorschau ausblenden Andere Handbücher für RPC-1.5FSR:

Werbung

DRAIN PIPING
14 DRAIN PIPING
Perfom the drain piping work after connecting the refrigerant
pipes and attaching insulations.
!
D A N G E R
Do not insert the drain pipe for the indoor unit to the drainage trench
where corrosive gases occur. Poisonous gases flow into the room,
so that may cause the poisoning.
?
N O T E
Do not create an upper-slope or rise for the drain piping, since drain
water can flow back to the indoor unit and leakage into the room will
occur when the system operation is stopped.
Do not connect the drain pipe with sanitary or sewage piping or any
other drainage piping.
When the common drain piping is connected with other indoor units,
the connected position of each indoor unit must be higher than the
common piping. The pipe size of the common drain pipe must be
large enough according to the unit size and number of units.
After performing drain piping work and electrical wiring, check to
ensure that water flows smoothly as in the following procedure.
If there is excessive clearance between the drain pipe connection and
the drain hose, add a sealing material between both parts in order to
fit and not deform the drain hose.
1 Connecting direction of drain pipe: the standard direction of
drain piping connection is right side as viewed from front.
However, it can be performed from the left side when it is
required due to building construction.
Left side
21
PMML0551 rev.1 - 02/2021 - A10762310A
For left side drain piping
Driver
Right side
(refrigerant pipe
connection)
2 Connecting drain hose.
a. Insert the hose into the hose clamp.
b. Push the drain hose onto the drain boss until the hose
c. Tighten the screw for hose clamp to face the screw part
d. Wrap the insulation (accessory) around the hose clamp
Left side
Cord clamp
Drain pan
Right side
Insert the drain plug into the
drain boss by using a driver.
Drain boss
Drain plug
Wrap the insulation around the
drain pipe connection.
Drain plug
Silicon sealant
reaches the end of drain pan. (If the drain hose is not
inserted completely, it causes water leakage.)
downward as shown in the figure below to prevent dew
drop.
to cover drain hose, drain pan, hose clamp without gap.
(If there is gap, dew drop may occur.)
Insulation
Drain plug
Remove the drain plug.

Werbung