• Connect or replace the unit's power fuse (100A) in the power cable connected to the auxiliary
battery.
• Replace the electronic control.
• Check and correct any poor contacts, splits, or disconnections in the power cable.
• Check and correct the position of the connection cables to the auxiliary battery (red cable to
+, and white cable to -).
• Check and correct any poor contacts in recirculation sensor terminals or cables. The
recirculation sensor is located under the front of the unit, next to the electronic control.
• Connect or replace the recirculation sensor.
• Repair any obstructions of the condenser fan; if the error persists, replace the condenser fan
(to access the condenser fan, first remove the unit's outer cover).
• Replace the 15A fuse. The condenser fan fuse is located in the electronic control under the
front of the unit.
• Repair any obstruction of the centrifugal blower; if the error persists, replace the blower (to
access the blower, first remove the unit's outer cover and the evaporator cover).
• Replace the 15A fuse. The centrifugal blower fuse is located in the electronic control under
the front of the unit.
TROUBLESHOOTING
Solution
EN
OPENAIR
13