OPENAIR
The control panel does not switch on
or the panel or the unit switches off
during operation.
When the unit is turned on, or during
operation, the control panel displays
warning
error). During this error, the unit will
be able to operate in ECO and AUTO
mode without temperature selection
and with the compressor at minimum
level. Press the On/Off button on the
panel or remote control once to turn
the unit off.
The control panel displays
Warning
error). With this warning, the unit
will be able to operate in ECO or
AUTO mode without temperature
selection and with the compressor at
minimum level. The warning will be
displayed on the control panel until
the anomaly is repaired.
During the unit's operation,
(blower error) is displayed on the
control panel and the unit goes off
automatically. The warning will be
displayed on the control panel until
the anomaly is repaired.
12
TU ESPACIO DE VIDA CONFORTABLE
TROUBLESHOOTING
DIAGNOSIS DE AVERÍAS
Symptom
(recirculation sensor
(electric fan
Cause
• Power fuse disconnected or cut out.
• Electronic control defective.
• Power cabling disconnected, cut or with poor
contact.
• Power cable polarity inverted.
• Poor connection in recirculation sensor cables or
terminals.
• Recirculation sensor disconnected or faulty.
• Condenser fan blocked, in short circuit or
disconnected.
• 15A fuse in condenser fan cut out.
• Centrifugal blower blocked in short circuit or
disconnected.
• 15A fuse in the blower cut out.