Technical specifications
Display
LED for switching status of relays per slot
Network interface
Supported protocols
User administration including rights management
LDAP(S)/Radius*/Active Directory connection
USB port for firmware update and data logging functions
CAN bus interface
CAN sensor types
Max. number of sensors per PDU
Plug & play drivers in the Rittal RiZone DCIM software
Conformity
Standards
Low Voltage Directive
EMC Directive
MTBF (at 40°C)
Protection category
Protection class
Contamination level
Overvoltage category
Storage temperature
Ambient temperatures
Ambient humidity
Connector latch C13 and C19
C13 covers included with supply
C19 covers included with supply
Warranty
Rittal PDU international/PDU UK power distribution unit
Safety
EMC
Technical specifications
OLED, RGB 128 x 128 pixels (not for Slave PDU
managed)
Yes (not for PDU metered)
RJ 45, integral web server (not for slave PDU man-
aged)
HTTP, HTTPS, SSL, SSH, NTP, Telnet, TCP/IP v4
and v6, DHCP, DNS, Syslog, SNMP v1, v2c and v3,
FTP/SFTP (update/file transfer), e-mail forwarding
(SMTP), LDAP, OPC-UA, Modbus/TCP, RFC (server
shutdown)
Yes
Yes
Yes (not for Slave PDU managed)
RJ 45, for connecting sensors
see section 6.3 "Connection of sensors"
4, sensor configuration freely selectable, including 4
of the same type (for PDU metered/switched/man-
aged)
Yes
CE
EN 60 950-1
EN 55 022/B, EN 61 000-4-2, EN 61 000-4-3,
EN 61 000-6-2, EN 61 000-6-3
2014/35/EU
2014/30/EU
70,000 hours
IP 20 (IEC 60 529)
3
1
II
-25°C...+70°C
0°C...+45°C
10...95% rel. humidity, non-condensing
1 x (further optional DK 7955.020), not for UK ver-
sions
8 x (further optional DK 7955.010), not for UK ver-
sions
3 x (further optional DK 7955.015), not for UK ver-
sions