Rittal PDU 7955.201 Installationsanleitung Und Kurz-Bedienungsanleitung Seite 32

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and operation of the slave PDU managed
Status change display on the multi-LED of the connected sensor.
– Continuous blue flashing: Communication via the CAN bus.
EN
– Green flashing: When the measured value changes or, at the latest, every 5 seconds.
Further sensors are connected as daisy chain.
If necessary, connect another component (e.g. another sensor type) to the second, free CAN bus
interface of the first component.
Proceed in the same way for further components (up to four units in total).
Note:
Further information concerning the connection and configuration of sensors can be found
in the associated documentation of the accessory part.
7
Installation and operation of the slave PDU managed
7.1
Operating and display elements
The operating and display elements are shown in fig. 16.
Key to fig. 16
1
CAN bus connection (daisy chain) for CMC III processing unit and CMC III sensors, 24 V
2
Second CAN bus connection, 24 V
3
Multi-LED for status display
7.2
Installation
Note:
To avoid malfunctions, please do not disconnect the PDU from the power supply during
the boot process.
Connect the PDU to a power supply with TN-S network configuration. Please note the detailed infor-
mation in section 8 "Technical specifications".
Depending on the PDU version, provide the following pre-fuse:
– PDU international: 3 x 16 A (3~/16 A versions), 3 x 32 A (3~/32 A versions), 1 x 16 A (1~/16 A ver-
sions) or 1 x 32 A (1~/32 A versions)
– PDU UK: 1 x 16 A (16 A versions) or 1 x 32 A (32 A versions)
– PDU UK: 1 x 13 A for PDU with BS 1363 (UK) plug
Route the PDU connection cable out of the IT rack and connect it to the mains supply.
Once connected, the multi-LED for the status display illuminates continually (fig. 16, item 3). The
LEDs of the CAN bus connections (fig. 16, items 1, 2) are flashing green or red.
Connect a connection cable from the Rittal accessories to a free slot on the PDU and the equipment.
Note:
When connecting the equipment, please note the maximum load per PDU slot (C13:
10 A, C19: 16 A, UK version: 13 A).
Depending on the PDU version, unused slots can be closed using the C13/C19 covers from the ac-
cessories (fig. 13).
32
Rittal PDU international/PDU UK power distribution unit