Rittal PDU 7955.201 Installationsanleitung Und Kurz-Bedienungsanleitung Seite 30

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Settings of the PDU metered/switched/managed
Alternatively, select the "DHCPv4" setting instead of "Manual" for automatic IP allocation.
Click on the Save button to change your settings.
EN
Change the network settings of your computer to its original values for the IP address and the subnet
mask.
Disconnect the network cable from your computer.
Connect the PDU to your Ethernet LAN with a network cable.
For any required software updates, please visit www.rittal.com or contact Rittal Service (see section 9).
6.3
Connection of sensors
Additional sensors may be connected to the intelligent PDUs for monitoring the ambient conditions in
the IT rack, so that alarms can be triggered if limits are exceeded. The following list shows all available
sensors with the relevant Model No. Regardless of the sensor type, the maximum number of sensors
is limited to 4 per PDU. Apart from the sensor itself, a sensor connection cable is also required and must
be ordered separately. This is available in various lengths. As well as the 4 sensors (maximum), up to 3
slave PDUs may also be connected.
As a minimum requirement, the PDU firmware V5.15.50 is required for full support of the sensors shown
in the list. Before installing the sensors, it may be necessary to update to this or a higher firmware ver-
sion.
CMC III/PDU sensor Model No: DK
7030.110
7030.111
7030.120
7030.130
7030.140
7030.150
7030.190
7030.400
7030.430
7030.440
7030.100
7030.500
7030.040
7030.050
7338.121
7338.321
7338.221
7859.050
7859.053
7859.312
7859.332
7859.410
7859.420
7859.430
30
Description
Temperature sensor
Temperature/humidity sensor
Infrared access sensor
Vandalism sensor
Analogue air flow sensor
Analogue differential pressure sensor
Universal sensor
Smoke alarm
Leak sensor
Leak sensor, 15 m
CAN bus sensor
Door control module
I/O unit
Power unit
DET-AC III extinguisher system master
DET-AC III extinguisher system slave
EFD III
PSM measurement bar 2 x 3 x 16 A
PSM measurement bar 1 x 32 A
MID measurement module 2 x 3 x 16 A
MID measurement module 2 x 3 x 32 A
PSM measurement module 8 x C13
PSM measurement module 4 x C19/2 x C13
PSM measurement module 4 x earthing-pin/2 x C13
Rittal PDU international/PDU UK power distribution unit