„ Devices without internal residual current
device must be connected via a separate
residual current device (see also
IEC 60364-7-722 (according to DIN
VDE 0100 722 in Germany).
„ Devices with integrated residual current
device are supplied with type B.
„ No other circuits may be connected to this
residual current device.
For the versions Start, Start E, Standard E and Basic E, the
required residual current device (RCD) must be provided
on site.
5.3.3 Laying the supply line
f All necessary lines to the location must be surface-
mounted or concealed.
Î Notes regarding the cables:
"5.5 Installing the device" and "5.6 Electrical connec-
tion"
Surface installation
MENNEKES recommends mounting the device on
an on-site cable duct
(height 30 mm × width 45 mm).
If the cables or cable duct comes from below, you have to
break out the pre-cut opening in the front enclosure part.
Concealed installation
In a concealed installation of wires, their positions must be
arranged in accordance with the drilling jig.
5.4 Opening the device
1
Fig.: 13. Opening the device
When delivered, the front enclosure part (2) is not attached
with screws. The screws (1) are stored in the enclosed
accessory bag.
f Ensure that the power supply is switched off.
f Remove the upper enclosure part (2).
f Remove screws (3) of front panel and fold down front
panel (4).
2
3
3
1
4
15
EN